When does a water heater need a drain pan, and what size is the drain?
A pan is required where a leak would cause damage; it must drain through a pipe at least 3/4 inch in diameter to an approved location (IRC P2801.6).
The IRC requires a drain pan under a storage-tank water heater installed where leaking water would cause damage — for example in an attic or above finished living space. The pan must be at least 1-1/2 inches (38 mm) deep.
The pan must drain through a pipe no smaller than 3/4 inch (19 mm) in diameter, running full-size to an indirect waste receptor or to the building exterior, where it ends 6 to 24 inches above grade.
The pan catches slow leaks and condensate. It is separate from, and not a substitute for, the relief-valve discharge line.
Verified against
Related answers
- Does a water heater need a temperature and pressure relief valve? — IRC §P2804
- How much combustion air does a gas furnace or water heater need indoors? — IRC §G2407.5
- Does a water heater or furnace in a garage have to be raised off the floor? — IRC §M1307.3
- Does every plumbing fixture need a P-trap? — IRC §P3201.6
- Do outdoor hose bibbs need a backflow preventer? — IRC §P2902.4.3
- What is the minimum shower size allowed by code? — IRC §P2708.1
- Do I need a permit to replace a water heater? — IRC §R105.1
Have a question about your own project?
Adopted edition and local amendments vary by city and county. Get answers with code references to verify against your local code.
Ask Donnie →General information based on the International Residential Code (a model code). This is AI assistance to verify — not legal advice. Confirm the adopted edition and any local amendments with your local building department (AHJ) and a licensed professional before you build.